Fire Extinguisher Storage and
Compliance Guide for Industrial Facilities
OSHA 1910.157 reference for EHS directors, facilities managers, and procurement officers — mounting requirements, inspection schedules, travel distances, and storage solutions.
Industrial facilities managing fire extinguisher compliance face four core requirements: correct mounting height (set by NFPA 10), travel distance by hazard class, documented monthly inspections, and annual maintenance (set by OSHA 1910.157). This guide covers each requirement with the specific code language, the current 2026 penalty schedule, and the storage configurations that keep large facilities audit-ready.
Blue SteelCo has built fire extinguisher storage racks for Class I railroads, engine manufacturers, steel mills, and 80+ industrial facilities since 1997. This guide is written by our engineering team and updated annually to reflect current OSHA penalty adjustments and NFPA 10 edition changes.
OSHA 29 CFR 1910.157 requires employers to mount, locate, and identify portable fire extinguishers so they are readily accessible, place them within 75 feet of Class A hazards and 50 feet of Class B hazards, conduct monthly visual inspections, and perform annual maintenance. NFPA 10 sets the mounting height: the top of the extinguisher no higher than 5 feet above the floor (3.5 feet for units over 40 lbs). Non-compliance penalties reach $16,550 per serious violation and $165,514 per willful violation in 2026.
Last Updated: March 2026 | Reviewed by: Blue SteelCo Engineering Team | Reading Time: 18 minutes
Fire extinguisher violations rank among OSHA's most frequently cited workplace safety infractions. In fiscal year 2025, portable fire extinguisher standards appeared on OSHA's top 10 most-cited list for general industry, and the agency's active Warehousing and Distribution Center National Emphasis Program (NEP) -- running through mid-2027 -- puts fire safety compliance under heightened scrutiny for warehouses, distribution centers, and manufacturing facilities nationwide.
This guide covers every requirement a facility manager, safety director, or EHS professional needs to know: the specific CFR citation numbers, the 2026 penalty amounts, the inspection schedules that trip up even experienced teams, and the storage solutions that keep your facility audit-ready year-round.
Table of Contents
-
Key Regulations Overview
-
Fire Extinguisher Mounting Height Requirements
-
Travel Distance Requirements
-
Monthly Inspection Requirements
-
Annual Maintenance and Long-Term Testing
-
Fire Extinguisher Storage Solutions
-
Industrial Pit Safety and Fall Protection
-
OSHA Penalties for Non-Compliance (2026)
-
Industries Most Affected
-
Frequently Asked Questions
-
Compliance Consultation
Key Regulations Overview
Three regulatory frameworks govern fire extinguisher placement, storage, and maintenance in general industry workplaces. Understanding where each applies prevents the overlapping violations that OSHA inspectors frequently stack during a single audit.
OSHA 29 CFR 1910.157 -- Portable Fire Extinguishers
This is the primary federal standard. It governs:
-
Selection and distribution (1910.157(d)) -- which types and how many extinguishers a facility needs based on hazard classification
-
Mounting and placement (1910.157(c) and (d)) -- accessibility and travel distance maximums; mounting heights come from NFPA 10
-
Inspection and maintenance (1910.157(e)) -- monthly checks, annual servicing, 6-year and 12-year testing cycles
-
Training (1910.157(g)) -- initial and annual employee training on proper extinguisher use
-
Hydrostatic testing (1910.157(f)) -- pressure testing requirements and schedules by extinguisher type
Employers who have an established emergency action plan under 29 CFR 1910.38 and who totally evacuate employees during fires may be exempt from certain requirements -- but they must still maintain extinguishers in specific areas such as those with Class B hazards.
OSHA 29 CFR 1910.28/29 -- Walking-Working Surfaces and Fall Protection
These standards govern guardrails, pit safety, and fall protection around floor openings -- directly relevant to facilities with maintenance pits, inspection trenches, and below-grade work areas where fire extinguishers may also be required.
-
1910.28(b)(3)(i) -- Employers must protect employees from falling through holes 4 feet or more above a lower level, using covers or guardrail systems. Service pits under 10 feet deep have their own exception under 1910.28(b)(8).
-
1910.29(b) -- Guardrail specifications: 42 inches (+/- 3 inches) top rail height, midrail at 21 inches, capable of withstanding 200 pounds of force
These requirements intersect with fire safety when maintenance pits and floor openings also serve as fire extinguisher staging areas, which is common in railroad shops, automotive service centers, and steel fabrication facilities.
NFPA 10 -- Standard for Portable Fire Extinguishers (2022 Edition)
While NFPA 10 is not itself a federal regulation, OSHA references it as the recognized consensus standard, and many state and local fire codes adopt it by reference. The current edition includes several provisions relevant to industrial facilities:
-
Section 6.1.3.8 -- Recognition of electronic monitoring systems as an acceptable alternative to monthly manual inspections, provided the system checks pressure, location, and obstruction status
-
Section 7.2.1 -- Annual maintenance must include a thorough examination of the mechanical parts, extinguishing agent, and expelling means
-
Section 8.3 -- Six-year internal examination requirements for stored-pressure extinguishers with dry chemical agents
-
Section 8.4 -- Twelve-year hydrostatic testing for all rechargeable extinguishers
The electronic monitoring provision in Section 6.1.3.8 is particularly relevant for large facilities managing dozens of extinguishers across multiple zones. Systems that meet the NFPA 10 criteria can reduce the manual inspection burden -- but they do not eliminate the annual professional maintenance requirement under OSHA 1910.157(e) (3).
Fire Extinguisher Mounting Height Requirements
OSHA 1910.157(c)(1) requires every portable fire extinguisher to be mounted, located, and identified so it is readily accessible without risk of injury. It does not set a height. The measurements come from NFPA 10, Section 6.1.3.8, which the International Fire Code and most state and local fire codes adopt.
Height Specifications
Extinguisher WeightMaximum Height (top of extinguisher)Minimum ClearanceSource
40 lbs or less (gross weight)5 feet (60 inches) from floor to top of extinguisher4 inches from floor to bottom of extinguisherNFPA 10, 6.1.3.8
Over 40 lbs (gross weight)3.5 feet (42 inches) from floor to top of extinguisher4 inches from floor to bottom of extinguisherNFPA 10, 6.1.3.8
Why These Numbers Matter
The 5-foot / 3.5-foot distinction exists because heavier extinguishers become dangerous to lift down from height. A 50-lb wheeled dry chemical unit mounted at 5 feet creates an injury risk that compounds the emergency it was meant to address.
The 4-inch minimum floor clearance serves two purposes: it prevents trip hazards from floor-level mounting and protects extinguisher bottoms from water damage during floor cleaning and from forklift impact in industrial environments.
Common Mounting Height Violations
-
Extinguishers sitting directly on the floor -- Violates the NFPA 10 4-inch minimum clearance. Common in facilities that removed wall brackets and never replaced them.
-
Extinguishers hung on hooks above doorframes -- Often exceeds the 5-foot maximum. Common in older buildings where original mounting points were set to outdated standards.
-
Extinguishers placed on top of cabinets or shelving -- Not only a height violation but also an accessibility problem under 1910.157(c)(1), which requires extinguishers to be "readily accessible." NFPA 10 also requires them to be conspicuously located.
-
Extinguishers stored loose in closets or storage rooms -- Violates mounting, height, accessibility, and visibility requirements simultaneously. This is the most expensive single citation scenario because each requirement is a separate potential violation.
Travel Distance Requirements
OSHA 1910.157(d) establishes the maximum distance any employee should have to travel to reach the nearest appropriate fire extinguisher. These distances are measured along the actual path of travel, not in a straight line.
Maximum Travel Distances by Hazard Class
Hazard ClassHazard TypeMaximum Travel DistanceOSHA Citation
Class AOrdinary combustibles: wood, paper, cloth, rubber, plastics75 feet1910.157(d) (2)
Class BFlammable liquids: gasoline, oil, grease, solvents, paints50 feet1910.157(d) (3)
Class CEnergized electrical equipmentPer underlying Class A or B hazard1910.157(d) (5)
Class DCombustible metals: magnesium, titanium, sodium, lithium75 feet1910.157(d) (6)
Class KCooking oils and fats (commercial kitchens)30 feet (per NFPA 10)NFPA 10, 6.6.1
Practical Application for Industrial Facilities
In a facility with mixed hazards -- which describes most manufacturing floors, warehouses, and distribution centers -- the most restrictive distance applies. If a warehouse stores flammable solvents (Class B) alongside paper products (Class A), extinguisher placement must satisfy the 50-foot Class B requirement throughout the area where both hazards are present.
Layout planning tip: For a 50,000-square-foot warehouse floor, travel distance compliance typically requires a minimum of 12-16 extinguishers depending on layout, obstruction patterns, and aisle configurations. Centralizing extinguishers into organized storage racks -- rather than scattering individual wall mounts -- can simplify compliance mapping while reducing the total units needed.
The Travel Distance Measurement Trap
OSHA measures travel distance along the actual walking path, not as a straight-line radius. This means aisles, racking, machinery, and other obstructions increase the effective travel distance. A fire extinguisher mounted 40 feet away in a straight line may be 65 feet away by walking path if employees must navigate around racking or equipment.
Facilities that change layouts frequently (seasonal inventory shifts, new equipment installations, production line reconfigurations) must re-evaluate travel distances after every significant change. This is one of the reasons mobile, repositionable storage solutions outperform fixed wall mounts in dynamic industrial environments.
Monthly Inspection Requirements
OSHA 1910.157(e)(2) requires monthly visual inspections of all portable fire extinguishers. These inspections can be performed by trained facility staff -- they do not require a certified fire protection technician.
What to Check During Monthly Inspections
-
Location and accessibility -- Extinguisher is in its designated location, not blocked by inventory, equipment, or vehicles
-
Pressure gauge -- Needle is in the green (charged) zone
-
Physical condition -- No visible damage, corrosion, dents, or leaks
-
Safety pin and tamper seal -- Intact and in place (indicates the extinguisher has not been discharged or tampered with)
-
Inspection tag -- Previous month's inspection is documented
-
Operating instructions -- Label is legible and facing outward
-
Fullness -- Lift or heft the extinguisher to confirm it has not been partially discharged (weight should match the weight listed on the label)
-
Nozzle/hose condition -- No blockage, cracking, or deterioration
Record-Keeping Requirements
OSHA 1910.157(e)(2) requires that the date of inspection and the initials of the inspector be recorded. The regulation does not prescribe a specific format, but the record must be retrievable for OSHA inspector review. Common methods include:
-
Hang tags attached to the extinguisher (most common)
-
Inspection logs maintained by the safety department
-
Electronic monitoring systems that meet NFPA 10 Section 6.1.3.8 criteria
-
Barcode/QR-code systems that log inspections to a central database
Critical note: A missing inspection tag is itself a citable violation, separate from any underlying maintenance deficiency. If an OSHA inspector pulls an extinguisher tag and finds gaps in the monthly inspection record, each missed month can be cited as a separate violation.
The Visibility Factor
Monthly inspections require that an inspector can visually verify extinguisher condition without removing the unit from its storage location. This is why NFPA 10 requires extinguishers to be conspicuously located -- and why storage solutions that allow visual inspection through expanded metal or open-frame construction eliminate a compliance step that enclosed cabinets cannot.
Annual Maintenance and Long-Term Testing
Beyond monthly inspections, OSHA 1910.157(e) (3)-(5) establishes a multi-year maintenance schedule that requires certified fire protection technicians.
Complete Maintenance Schedule
IntervalRequirementPerformed ByOSHA / NFPA Citation
MonthlyVisual inspection (8-point check above)Trained facility staffOSHA 1910.157(e) (2)
AnnuallyProfessional maintenance examinationCertified technicianOSHA 1910.157(e) (3)
Every 6 yearsInternal examination (stored-pressure dry chemical)Certified technicianOSHA 1910.157(e) (4), NFPA 10 8.3
Every 12 yearsHydrostatic pressure test (all rechargeable types)Certified technicianOSHA 1910.157(f), NFPA 10 8.4
Annual Maintenance: What the Technician Checks
The annual maintenance inspection goes beyond the monthly visual check. Per OSHA 1910.157(e)(3) and NFPA 10 Section 7.2.1, a certified technician must:
-
Examine all mechanical parts (handles, levers, triggers, locking mechanisms)
-
Verify the extinguishing agent is the correct type and has not degraded
-
Inspect the expelling means (nitrogen cartridge, stored pressure, CO2 cylinder)
-
Check for internal corrosion or contamination
-
Verify the unit's weight against the manufacturer specification
-
Replace or repair any deficient components
-
Attach a new annual service tag with the technician's certification number
6-Year and 12-Year Testing
The 6-year internal examination under OSHA 1910.157(e)(4) applies to stored-pressure dry chemical extinguishers. The technician empties the agent, inspects the interior for corrosion or damage, reassembles, recharges, and verifies proper operation.
The 12-year hydrostatic test under OSHA 1910.157(f) applies to all rechargeable extinguishers. The cylinder is pressurized to test its structural integrity. Extinguishers that fail hydrostatic testing must be removed from service and destroyed -- they cannot be repaired.
Fire Extinguisher Storage Solutions
How a facility stores its fire extinguishers directly affects compliance with OSHA 1910.157's accessibility and inspection requirements and NFPA 10's visibility and mounting height requirements. The choice of storage method impacts both audit readiness and operational efficiency.
Storage Methods Compared
-
MethodBest ForAdvantagesDisadvantages
-
Wall-mounted bracketsSingle extinguishers in fixed locationsLow cost, simple installationLimited capacity, requires wall space, inflexible when layouts change
-
Recessed or surface cabinetsHarsh environments, high-traffic corridorsProtects from damage, clean appearanceObstructs visual inspection (door must be opened), higher cost per unit
-
Floor standsTemporary or relocatable placementsPortable, no installation neededUnstable, easily knocked over, limited to 1-2 units
-
Industrial storage racksFacilities with 6+ extinguishers per zoneHigh capacity, visual inspection through expanded metal, centralized complianceRequires floor space, higher upfront investment
Why Industrial Storage Racks Solve the Compliance Problem
Facilities managing a dozen or more extinguishers face a compounding compliance burden: every unit needs its own wall bracket, every bracket needs correct mounting height, every location needs clear signage, and every unit needs monthly inspection access. Wall-mounted configurations spread compliance obligations across dozens of locations, each of which can generate a separate OSHA citation.
Centralized industrial storage racks consolidate these obligations. A single 24-place fire extinguisher storage rack puts 24 units in one place, visible and within reach, with:
-
Correct mounting height built into the rack design
-
Visual inspection access through expanded metal construction -- inspectors verify charge status without removing units
-
Centralized inspection routing -- one stop during monthly walkthroughs instead of 24 scattered locations
-
Bolt-down and tie-down mounting that meets seismic and forklift-traffic stability requirements
-
Safety yellow powder coating for high visibility
Blue SteelCo builds fully welded, American-made fire extinguisher storage racks, in configurations from 6-place to 48-place capacity. Every rack ships fully welded -- no field assembly required. Free shipping is standard on all orders.
For facilities where wall-mounting is the better fit (corridor placements, stairwells, individual workstations), traditional brackets remain the right answer. But for warehouse floors, manufacturing zones, loading docks, and any area managing multiple extinguishers, purpose-built storage racks eliminate the category of violations that come from improvised storage.
Industrial Pit Safety and Fall Protection
Fire safety and fall protection regulations intersect wherever maintenance pits, inspection trenches, and floor openings exist in industrial facilities. OSHA treats the pit edge and the pit stairs as two separate requirements, and facilities that manage fire extinguisher compliance often overlook one of them.
The Pit Edge
Under OSHA 1910.28(b)(3)(i), employers must protect employees from falling through holes 4 feet or more above a lower level, using covers or guardrail systems. Service pits have their own rule: under 1910.28(b)(8), pits under 10 feet deep need no edge fall protection while access is limited to authorized employees, the floor is marked 6 feet from the edge, and "Caution - Open Pit" signs are posted. Openings where the edge rule applies include:
-
Vehicle maintenance pits in railroad shops, fleet garages, and service centers
-
Inspection trenches in manufacturing and assembly facilities
-
Below-grade access points in steel mills, chemical plants, and refineries
-
Equipment pits housing hydraulic systems, conveyors, or electrical infrastructure
Guardrail Specifications (OSHA 1910.29(b))
-
RequirementSpecification
-
Top rail height42 inches (+/- 3 inches) from walking surface
-
Mid rail height21 inches (halfway between top rail and walking surface)
-
Force resistanceMust withstand 200 lbs of force in any outward or downward direction
-
Toe boardRequired where objects could fall onto workers below (3.5 inches minimum height; 2.5 inches allowed around vehicle repair, service, and assembly pits)
-
SurfaceSmooth, no snag points on clothing or skin
The Pit Stairs
The stairs into a pit are a separate requirement. OSHA 1910.28(b)(11) requires a stair rail on stairs with at least 3 treads and 4 risers, and 1910.29(f) sets the criteria. The pit edge exception does not cover the stairs.
A fixed stair rail blocks vehicles that need to cross the pit, so it gets unbolted and leaned against a wall, and the stairs go without a rail.
Blue SteelCo's collapsible pit handrail folds below the floor plane for vehicle crossings and extends onto the stairs in under 60 seconds. The 34-inch top rail serves as both stair rail and handrail, designed to support compliance with OSHA 1910.28(b)(11) and 1910.29(f). It is a stair rail, not a pit-edge guardrail. Under OSHA's February 26, 2026 interim enforcement guidance for 1910.29(f), a stair rail top rail of 30-38 inches may also serve as the handrail on systems installed before a final rule takes effect. Stair rail heights are under active OSHA rulemaking (2021 NPRM); verify current requirements at installation.
OSHA Penalties for Non-Compliance (2026)
OSHA adjusts penalty amounts annually for inflation under the Federal Civil Penalties Inflation Adjustment Act. OSHA made no inflation increase for 2026, so the 2025 amounts remain in effect.
Current Penalty Amounts
-
Violation TypeMaximum Penalty Per ViolationDescription
-
Serious$16,550A violation where there is substantial probability that death or serious physical harm could result
-
Other-Than-Serious$16,550A violation with direct relationship to job safety/health but probably would not cause death or serious harm
-
Willful$165,514A violation committed with intentional knowing or voluntary disregard, or with plain indifference
-
Repeated$165,514A violation of any standard where the employer has been previously cited for a substantially similar violation
-
Failure to Abate$16,550 per dayAssessed for each calendar day beyond the abatement date
-
Posting Requirements$16,550Failure to post required OSHA notices and citations
How Violations Stack
A single OSHA inspection can produce multiple citations from one walk-through. Fire extinguisher violations compound because each specific deficiency is citable independently:
Example scenario: An inspector finds 10 fire extinguishers in a warehouse. Three are blocked by pallets (accessibility violation), two have expired inspection tags (maintenance violation), and one is mounted at 6 feet (height violation). That is potentially 6 separate serious violations -- up to $99,300 in penalties from a single inspection area.
Under the Warehousing NEP, OSHA compliance officers are specifically trained to check fire extinguisher compliance as part of the programmed inspection protocol. Warehousing and distribution facilities selected for NEP inspections face comprehensive audits, not spot checks.
Penalty Reduction Factors
OSHA may reduce penalties based on:
-
Employer size -- Up to 60% reduction for employers with 25 or fewer employees
-
Good faith -- Up to 25% reduction for demonstrated commitment to safety (written programs, training records, self-audits)
-
History -- Up to 10% reduction for employers with no serious citations in the past 5 years
These reductions apply to serious violations only. Willful and repeated violations are not eligible for good-faith reductions.
Industries Most Affected
While OSHA 1910.157 applies to all general industry workplaces, certain industries face disproportionate fire extinguisher compliance challenges due to facility size, hazard density, and operational complexity.
Railroad and Transit Maintenance
Railroad maintenance shops combine Class A, B, and D fire hazards with large floor plans and maintenance pits that require both fire extinguisher placement and fall protection. The Federal Railroad Administration (FRA) enforces additional fire safety requirements that layer on top of OSHA standards.
Steel and Metal Fabrication
Welding operations, cutting torches, and combustible metal dust create Class A, B, and D hazards often within the same work cell. Travel distance compliance is challenging because extinguisher placement must account for multiple hazard classes simultaneously.
Chemical and Petrochemical
Flammable liquid storage, processing, and handling create Class B hazards that require the more restrictive 50-foot travel distance across large facility footprints. Chemical plants also face Process Safety Management (PSM) requirements under 1910.119 that intersect with fire protection.
Warehousing and Distribution
The active OSHA Warehousing NEP (CPL 03-00-027) makes fire extinguisher compliance an inspection priority through mid-2027. Facilities with dynamic inventory layouts face ongoing travel distance recalculation as storage configurations change seasonally.
Manufacturing
Manufacturing floors with mixed operations -- machining, painting, assembly, packaging -- present multiple hazard classes that require careful extinguisher selection and placement. Layout changes during production line reconfigurations frequently create temporary compliance gaps.
Frequently Asked Questions
What is the OSHA mounting height for fire extinguishers?
OSHA 1910.157 does not set a mounting height; 1910.157(c)(1) requires extinguishers to be mounted, located, and identified so they are readily accessible. The heights come from NFPA 10, Section 6.1.3.8, which the International Fire Code and most state and local fire codes adopt: extinguishers 40 pounds or less mount with the top no higher than 5 feet (60 inches) above the floor; over 40 pounds, no higher than 3.5 feet (42 inches). The bottom must be at least 4 inches above the floor.
What is the maximum travel distance to a fire extinguisher?
Under OSHA 1910.157(d), the maximum travel distance is 75 feet for Class A hazards (ordinary combustibles) and 50 feet for Class B hazards (flammable liquids). These distances are measured along the actual walking path, not in a straight line. Class C (electrical) hazards defer to the underlying Class A or B distance. Class D (combustible metals) allows 75 feet.
How often must fire extinguishers be inspected?
OSHA 1910.157(e) requires four tiers of inspection: monthly visual inspections by trained facility staff, annual maintenance examinations by a certified technician, 6-year internal examinations for stored-pressure dry chemical extinguishers, and 12-year hydrostatic pressure tests for all rechargeable units. Monthly inspections must be documented with the date and inspector initials.
What is the OSHA fine for fire extinguisher violations in 2026?
Serious violations carry a maximum penalty of $16,550 per violation. Willful or repeated violations can reach $165,514 per violation. Failure to abate costs up to $16,550 per day beyond the correction deadline. Multiple deficiencies found during a single inspection can be cited separately, so a facility with several extinguisher issues can face tens of thousands of dollars in combined penalties.
Can I use electronic monitoring instead of monthly manual inspections?
NFPA 10 Section 6.1.3.8 recognizes electronic monitoring systems as an acceptable alternative to monthly manual inspections, provided the system continuously monitors pressure, location, and obstruction status. However, electronic monitoring does not replace the annual professional maintenance examination required under OSHA 1910.157(e) (3). The system must also meet specific performance criteria outlined in NFPA 10.
Do I need fire extinguishers if my building has a sprinkler system?
Yes. OSHA 1910.157(c) (2) allows limited exemption only when an employer has an emergency action plan under 1910.38 and a policy of total employee evacuation. Even then, extinguishers are still required for certain Class B hazard areas. A sprinkler system alone does not exempt a facility from portable fire extinguisher requirements.
What does OSHA require at maintenance pits?
OSHA treats the pit edge and the pit stairs separately. Under 1910.28(b)(8), service pits under 10 feet deep need no edge fall protection while access is limited to authorized employees, the floor is marked 6 feet from the edge, and "Caution - Open Pit" signs are posted; otherwise guardrails or covers apply, and 1910.29(b) guardrails have a 42-inch (+/- 3 inches) top rail that withstands 200 pounds. The pit stairs need a stair rail under 1910.28(b)(11). Collapsible stair rails cover the pit stairs, not the pit edge, and fold below the floor plane for vehicle access.
How do I know which type and size of fire extinguisher I need?
OSHA 1910.157(d)(1) requires a hazard assessment to determine fire classes present in each area. Class A hazards need water or dry chemical extinguishers, Class B needs dry chemical or CO2, Class C needs non-conductive agents (dry chemical or CO2), and Class D needs specialized agents matched to the specific metal. NFPA 10 Table 6.2.1.1 provides minimum extinguisher ratings by hazard level (light, ordinary, extra).
What is the Warehousing NEP and how does it affect my facility?
The OSHA Warehousing and Distribution Center National Emphasis Program (CPL 03-00-027) is an active enforcement initiative running through mid-2027 that targets warehousing operations for programmed inspections. Fire extinguisher compliance is part of the standard inspection protocol. Facilities selected for NEP inspections receive comprehensive audits covering fire safety, powered industrial trucks, walking-working surfaces, and ergonomic hazards.
Are fire extinguisher storage racks required by OSHA?
OSHA does not mandate a specific storage method. 1910.157(c)(1) requires extinguishers to be readily accessible, and 1910.157(c)(4) requires them to be kept in their designated places; NFPA 10 adds conspicuous location, mounting heights, and protection from damage. Industrial storage racks are one way to meet all of these at once, particularly in facilities managing 6 or more extinguishers per zone. The key is that whatever storage method you choose must meet all accessibility, height, visibility, and protection requirements.